Description
Type no.: 20002205
Promotion code: 80190777
UNSPSC (v. 19.0501): 26121634
HS Code: 85446010
Application:
Fire safe, halogen-fee and screened cable for fixed installation in-doors , in pipes, trays and in cement. Applicable where demands for fire safetey >30 minutes is required.
Fire properties:
FIre retardand: Yes, DIN EN 50266-1 & -2-4, IEC 60332-1 & 3
Fire safe: Yes, IEC 60331, DIN 4102-12, E30
Halogen-free: Yes, IEC 60754-1-2
Low smoke density: Yes, IEC 61034
Current load: Acc. to SB 2001:6 - Especially good varmth transferance
Construction:
Conductor: Single or multi-stranded round copper acc. to IEC 60228 class 1 & 2
Insulation: Silicone and H-EPR
Color code 2-conductor: Blue, brown
Color code 3-conductor: Blue, brown, G/Y
Color code 4-conductor: Brown, black, grey , G/Y
Color code 5-conductor: Blue, brown, black, grey, G/Y
Color code >5-conductor: G/Y, black, with white numbering
Inner sheath: Extrudered
Screen: Overlappeing copper foil with concentric screen of copper wire.
Outer sheath: Halogen-free compound, orange
Technical data:
Rated voltage: 0,6/1 kV
Test voltage: 4000 V
Max. conductor temperature: +90˚C
Short circuit temperature: +250˚C
Min. temperature during installation: -5°C
Bending radius: 1-conductor 15 x D, Multi-conductor 12 x D
Standard: DIN VDE 0266, 0276-604 & DIN 4102-12
Direktive: CE marked, complies with LVD, RoHS and REACH
This article is approved for use in installations that has the Swanlabel 'Svanemærket' and for DGNB certified contrucktion work
Fire safe, halogen-fee and screened cable for fixed installation in-doors , in pipes, trays and in cement. Applicable where demands for fire safetey >30 minutes is required.
Fire properties:
FIre retardand: Yes, DIN EN 50266-1 & -2-4, IEC 60332-1 & 3
Fire safe: Yes, IEC 60331, DIN 4102-12, E30
Halogen-free: Yes, IEC 60754-1-2
Low smoke density: Yes, IEC 61034
Current load: Acc. to SB 2001:6 - Especially good varmth transferance
Construction:
Conductor: Single or multi-stranded round copper acc. to IEC 60228 class 1 & 2
Insulation: Silicone and H-EPR
Color code 2-conductor: Blue, brown
Color code 3-conductor: Blue, brown, G/Y
Color code 4-conductor: Brown, black, grey , G/Y
Color code 5-conductor: Blue, brown, black, grey, G/Y
Color code >5-conductor: G/Y, black, with white numbering
Inner sheath: Extrudered
Screen: Overlappeing copper foil with concentric screen of copper wire.
Outer sheath: Halogen-free compound, orange
Technical data:
Rated voltage: 0,6/1 kV
Test voltage: 4000 V
Max. conductor temperature: +90˚C
Short circuit temperature: +250˚C
Min. temperature during installation: -5°C
Bending radius: 1-conductor 15 x D, Multi-conductor 12 x D
Standard: DIN VDE 0266, 0276-604 & DIN 4102-12
Direktive: CE marked, complies with LVD, RoHS and REACH
This article is approved for use in installations that has the Swanlabel 'Svanemærket' and for DGNB certified contrucktion work