Active arc fault detection circuit breaker, Acti9 iC40N ARC, 1P+N, 13A, B curve, 6000A Image #0

Active arc fault detection circuit breaker, Acti9 iC40N ARC, 1P+N, 13A, B curve, 6000A

  • EAN no.: 3606481906199
  • LM no.: 3322050858
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no: A9TPDD613

Promotion code: 80080487230

UNSPSC (v. 19.0501): 39121614

HS Code: 85362010

This Acti9 Active iC40 ARC product is an arc fault detection circuit breaker. It is a 1P+N with 1 protected pole, 13A In rated current and B tripping curve. The rated short circuit breaking capacity goes up to 6000A at 230VAC conforming to EN/IEC 60898-1 standard and 10kA at 230VAC conforming to EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit, overload current and arc fault. Its fast closing mechanism independent of manual operation improves its service life. The Acti9 Active products communicate with the gateway EcoStruxure Panel Server Entry, Universal and Advanced. Its pre alarming system can prevent any overload, earth leakage and overvoltage. It can also measure the voltage, the current and the power. Its 2 unique VisiTrip indicators reduce intervention time by showing the faulty circuit and identifying quickly the type of default. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 250VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 2. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 91mm x (D)73mm. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. This product is compliant with EN/IEC 62606, EN/IEC 60898-1 and EN/IEC 60947-2 standard.

Specifications

Pollution degree
2
Current limiting class
3
Over voltage category
3
Rated short-circuit breaking capacity according to IEC 60947-2
10
Rated short-circuit breaking capacity according to EN 60898
6
Additional equipment attached at delivery
Fire protection switch
Concurrently switching neutral conductor
TRUE
Release characteristic
B
Frequency
50 - 50
Built-in depth
44