Air Purge Kit. Image #0

Air Purge Kit.

  • EAN no.: 5710147431340
  • LM no.: 7885503107
  • Supplier: Carrier Fire & Security Danmark A/S
Must login for adding to cart

Description

Type no: FF-AP2N

Promotion code: 80140933010

UNSPSC (v. 19.0501): 46191511

HS Code: 73269098

The Air Purge kit is intended to be mounted in between a Flameproof (ExD) Flame Detector (FF7x series - Exd versions) and adjustable mounting bracket (FF705), with the Air Purge kit nozzle positioned to channel air from the inlet onto the window of the flame detector to prevent obscuration by particles.
Successor of FF-AP2
Mounting
The Air Purge nozzle must be angled at 45° from horizontal in order to maximize the air flow over the front window.
Installation
The purge air adapter should be connected to an external air supply via the female 1/4” BSP non return valve.
The air should be oil free and dry with a pressure range from 7psi (0.5Bar) to 50psi (3.5Bar).
If the air is not required continuously to keep the viewing window clean then a pulse of air can be supplied at regular intervals.
Caution: This product is not suitable for use in ATEX zone 0 - For use in ATEX zone 1/21 or 2/222, air must be clean and the system blown through before placing in a hazardous environment.

Specifications

Product Series
FF
Brand
Kidde Commercial
Variant
Air Purge
Standard
EN54 - Ej godkendt
kg CO2 (Production)
22536 (Proxy beregnet)