Electronic over current relays, TeSys LT47, automatic, 0.5 to 6A, 200 to 240VAC Image #0

Electronic over current relays, TeSys LT47, automatic, 0.5 to 6A, 200 to 240VAC

  • EAN no.: 3389110576559
  • LM no.: 7522460804
  • Supplier: Schneider Electric
Login to add product to cart.

Description

Type no.: LT4706M7A

Promotion code: 80080460225

UNSPSC (v. 19.0501): 39122325

HS Code: 85364900

TeSys LR47 electronic overcurrent relay, 6A/690V, with automatic reset, to be supplied with 200-240V AC, for protection of motors with a rated current 0.5-5A. It provides 3 dials to adjust the protection, LOAD (0.5-6A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, R-TIME (1-120sec) for the automatic reset delay. In addition, the device trips when there is a missing phase during more than O-TIME. The device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO+1NC for fault signaling. Settings can be locked by sealing the transparent cover. DIN rail mounting, without power terminals (currents monitored by 2 current transformers crossed by the motor cables). Multi standards certified (IEC, UL, CSA, CCC, EAC), it conforms to RoHS/REACh regulation.

Specifications

Adjustable current range
0.5 - 6
Brand
Schneider Electric
Depth
77.2
External power supply required
FALSE
Height
70.3
kg CO2 (Production)
1,23 (Proxy beregnet)
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
1
Number of auxiliary contacts as normally open contact
1
Operating voltage AC 50 Hz
200 - 240