Electronic over current relays, TeSys LT47, manual, 3 to 30A, 24VAC/DC Image #0

Electronic over current relays, TeSys LT47, manual, 3 to 30A, 24VAC/DC

  • EAN no.: 3389110576580
  • LM no.: 7522460684
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no.: LT4730BS

Promotion code: 80080460225

UNSPSC (v. 19.0501): 39122325

HS Code: 85364900

TeSys LR47 electronic overcurrent relay, 30A/690V, with manual reset, to be supplied with 24V AC/DC, for protection of motors with a rated current 3-25A. It provides 3 dials to adjust the protection, LOAD (3-30A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when there is a missing phase during more than O-TIME. The device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO+1NC for fault signalling. Settings can be locked by sealing the transparent cover. DIN rail mounting, without power terminals (currents monitored by 2 current transformers crossed by the motor cables). Multi standards certified (IEC, UL, CSA, CCC, EAC), it conforms to RoHS/REACh regulation.

Specifications

External power supply required
FALSE
Reset function push-button
TRUE
Reset function input
FALSE
Reset function automatic
FALSE
Operating voltage DC
24 - 24
Operating voltage AC 60 Hz
24 - 24
Operating voltage AC 50 Hz
24 - 24
Adjustable current range
3 - 30
Voltage type (operating voltage)
AC/DC
Voltage type for actuating
AC/DC