Installation cable HFALS Dca 4x240 T600
- EAN no.: 5714969017218
- LM no.: 5733153339
- Supplier: DANCABLES ApS
Must login for adding to cart
Description
Type no.: 52030155
Promotion code: 80090590027
UNSPSC (v. 19.0501): 26121615
HS Code: 85446010
Application: Halogen-free installation cable in CPR Dca for fixed installation indoors and outdoors, as well as in the ground.
Must be installed according to HD 60364.
Conductor: Round stranded aluminum according to IEC60228 class 2
Conductor Insulation: PEX
Conductor Identification: Color code according to HD 308
Filling Sheath: Halogen-free compound
Outer Sheath: Gray halogen-free compound
Complies with RoHS CE compliance Low Voltage Directive UV resistant
Rated Voltage: 0.6/1 kV
Test Voltage: 4 kV
Current Rating: According to SB
Minimum Bending Radius: 12X D
Handling Temperature: Min 5°C
Conductor Temperature: Max 90°C
Short Circuit Temperature: Max 250°C
Self-extinguishing: IEC 60332-1
Halogen-free: IEC 60754-1, -2
Smoke Density: IEC 61034
Standard: HD 604 S1
Must be installed according to HD 60364.
Conductor: Round stranded aluminum according to IEC60228 class 2
Conductor Insulation: PEX
Conductor Identification: Color code according to HD 308
Filling Sheath: Halogen-free compound
Outer Sheath: Gray halogen-free compound
Complies with RoHS CE compliance Low Voltage Directive UV resistant
Rated Voltage: 0.6/1 kV
Test Voltage: 4 kV
Current Rating: According to SB
Minimum Bending Radius: 12X D
Handling Temperature: Min 5°C
Conductor Temperature: Max 90°C
Short Circuit Temperature: Max 250°C
Self-extinguishing: IEC 60332-1
Halogen-free: IEC 60754-1, -2
Smoke Density: IEC 61034
Standard: HD 604 S1