Long time rating plug ComPacT NS IEC MicroLogic control units standard setting (Ir = In x 0.4 to 1) Image #0

Long time rating plug ComPacT NS IEC MicroLogic control units standard setting (Ir = In x 0.4 to 1)

  • EAN no.: 3606482098596
  • LM no.: 3322752172
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no: C33542

Promotion code: 80080488250

UNSPSC (v. 19.0501): 39121601

HS Code: 85389091

This component is an interchangeable plug for MicroLogic control units. It is used to limit the long-time threshold setting range for higher accuracy (pick-up and delay). The long-time pickup switch sets the maximum current level (Ir) the circuit breaker will carry continuous within the range 0.4 to 1 x In. There are 9 possible settings (0.4 , 0.5 , 0.6 , 0.7 , 0,8 , 0.9 , 0.95 , 0.98 , 1). The long-time delay switch sets the length of time that the circuit breaker will carry a sustained overload before tripping. Delay bands are labelled in seconds of overcurrent at six times the ampere rating (6 x Ir). ComPacT NS new generation is part of Schneider Electric EcoStruxure Power architecture. ComPacT NS new generation is more sustainable with green packaging and green partnerships.

Specifications

Type of accessory/spare part
Other
Product Series
Compact
Brand
Schneider Electric
Spare part
TRUE
Accessory
TRUE
kg CO2 (Production)
0,06 (Proxy beregnet)