Power Cable FXQJ EMC 4x16+16 Dca AFM Image #0

Power Cable FXQJ EMC 4x16+16 Dca AFM

  • EAN no.: 7394479022070
  • LM no.: 3033401990
  • Supplier: Nkt Cables
Must login for adding to cart

Description

Type no.: 112726017D0500

Promotion code: 80090716020

UNSPSC (v. 19.0501): 26121634

HS Code: 85444995

Intended use:
Cables according to this standard are halogen free and flame retardant. In case of fire, only smoke free of corrosive gases and with low smoke density are emitted. Intended for permanent installation in- and outdoors, in ground and in pipes. Caution shall be taken into account if plowing. Registered in the Building Materials Database and can be included in a Nordic Swan Ecolabelled building.

Construction:
Conductor: Annealed copper according to IEC 60228 class 2 2,5-50 mm²: Round 70-240 mm²: Sector shaped
Insulation: XLPE Colour identification: 3-core: brown, black, grey 4-core: blue, brown, black, grey
Cu foil
Screen: Annealed copper wires
Sheath: Black halogen free flame retardant polyolefine Example of marking: FXQJ 0,6/1 kV 4x25/16 and meter marking

Properties:
Rated voltage 0,6/1 kV
Maximal short circuit temperature 250 °C
Minimum temperature during installation. Caution shall be taken into account at temperatures below 0 °C. -20 °C
Maximum conductor temperature 90ºC
Minimum bending radius 8 x D
Maximum pulling force when connected to all conductors 50 N/mm2
Fire classification Dca -s2, d2, a2
Fulfills the low voltage directive: Yes
Fulfills RoHS: Yes
Fulfills REACH: Yes

Specifications

Low smoke according to EN IEC 61034-2
TRUE
Halogen free according to EN IEC 60754-2
TRUE
Concentric conductor
Copper
Max. conductor temperature
90
Protective barrier
None
Drain wire
FALSE
Lead sheath
FALSE
Suitable for underground installation
TRUE
Reaction-to-fire according to EN 13501-6: Acidity
a2
Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
d2

Documents and Links