Shunt trip coil for NSXm and PP-B 24V AC/DC Image #0

Shunt trip coil for NSXm and PP-B 24V AC/DC

  • EAN no.: 3606485413174
  • LM no.: 3322730592
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no: LV426861

Promotion code: 80080488245

UNSPSC (v. 19.0501): 39121601

HS Code: 85363010

This pre-wired MX shunt trip is used on Compact NSXm and PowerPact B devices. This auxiliary is used for emergency off or failsafe remote opening applications. It is a one click spring type auxiliary for quick and easy installation, visible from the front face of the device. This MX auxiliary has a 24 VAC 50/60Hz or 24VDC rated voltage. It trips the circuit breaker when the control voltage rises above 70% of its rated value. It complies with IEC 60947-2 standard. Compact NSXm and PowerPact B embed either 1 MN or 1 MX coil. PowerPact B-frame circuit breaker accessory, LV426861, offers proven performance, flexibility, and reliability. This PowerPact Molded Case Circuit Breaker accessory is an undervoltage release. A voltage release can be used to trip the circuit breaker using a control signal. Shunt trips serve primarily for remote, emergency-off commands. Undervoltage releases disconnect under low-voltage conditions. With a 0.35...0.7 x Un Threshold tripping voltage and a response time of <50 ms.

Specifications

Suitable for power circuit breaker
TRUE
Suitable for motor safety switch
FALSE
Suitable for off-load switch
TRUE
Suitable for overload relay
FALSE
Voltage type for actuating
AC/DC
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0
Number of contacts as change-over contact
0
Power consumption
5
Rated control supply voltage AC 60 Hz
24 - 24