TeSys D contactor LC1D65ABD 3P 65A AC-3 30kW@400V 1NO+1NC aux contact 24V DC coil Image #0
TeSys D contactor LC1D65ABD 3P 65A AC-3 30kW@400V 1NO+1NC aux contact 24V DC coil Image #1
TeSys D contactor LC1D65ABD 3P 65A AC-3 30kW@400V 1NO+1NC aux contact 24V DC coil Image #0
TeSys D contactor LC1D65ABD 3P 65A AC-3 30kW@400V 1NO+1NC aux contact 24V DC coil Image #1
Schneider Electric

TeSys D contactor LC1D65ABD 3P 65A AC-3 30kW@400V 1NO+1NC aux contact 24V DC coil

  • EAN no.: 3389119409094
  • LM no.: 7522510220
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no.: LC1D65ABD

Promotion code: 80080470203

UNSPSC (v. 19.0501): 39121529

HS Code: 85364190

LC1D65ABD is a 3-pole TeSys D contactor from Schneider Electric for motor applications up to 30kW@400V. It includes a 24V DC coil and 1NO+1NC built-in auxiliary contacts, it can be used in all control systems and safety applications thanks to its certified NC mirror contact. Compact, DIN-rail mounting, it procures high reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 55mm wide, for DIN-rail and panel mounting
. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections
. Equipped with a 24V DC coil for easy integration to all control systems
. Provides 2 built-in auxiliary contacts 1NO + 1NC, NC is a certified mirror contact suitable to be included in the control of safety systems
. High electrical durability, guaranteed for 1.6 million cycles at 65A AC-3 440V, for demanding motor switching applications
. Robust design with high making and breaking capacities up to 20 In
. Power connections by EverLink BTR screw terminals providing constant tightening pressure

Specifications

Modular version
FALSE
Voltage type for actuating
DC
Type of electrical connection of main circuit
Screw connection
Rated operation current Ie at AC-4, 400 V
25
Rated operation power at AC-4, 400 V
11
Depth
120
Number of auxiliary contacts as normally closed contact
1
Number of auxiliary contacts as normally open contact
1
Number of normally closed contacts as main contact
0
Number of normally open contacts as main contact
3