Description

Type no.: GV2L04

Promotion code: 80080464215

UNSPSC (v. 19.0501): 39122215

HS Code: 85362090

TeSys GV2, Circuit breaker, magnetic, 0,63A, screw clamp terminals. range: TeSys - product name: TeSys GV2 - device short name: GV2L - product or component type: circuit breaker - device application: motor - network type: AC - utilisation category: category A conforming to IEC 60947-2, AC-3 conforming to IEC 60947-4-1 - breaking capacity: 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 - [Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 - magnetic tripping current: 8 A. Benefits: Complete protection concentrated in a single product. Compact and simple to select, TeSys GV2motor circuit-breakers are only 45mm wide and are categorized according to their level of performance and functions: type of control, breaking capacity, motor protection and accessories.... Applications: - Industry, infrastructure, building, etc:, Motor control and protection, in accordance with standards IEC 947-2 and IEC 947-4-1., Easily inserted in any configuration by screw or clip-fixing onto mounting rails..

Specifications

Device construction
Complete device in housing
Adjustment range undelayed short-circuit release
8 - 8
Switch off technique
Magnetic
Rated operation power at AC-3, 230 V
0.09
Type of electrical connection of main circuit
Screw connection
Degree of protection (IP)
IP20
Rated short-circuit breaking capacity lcu at 400 V, AC
100
Power loss
1.8
Depth
97
Rated permanent current Iu
0.63