Zelio control relay for 3-phase detection of undervoltage and phase-fault 2C/O 8A 3x400VAC Image #0
Zelio control relay for 3-phase detection of undervoltage and phase-fault 2C/O 8A 3x400VAC Image #1
Zelio control relay for 3-phase detection of undervoltage and phase-fault 2C/O 8A 3x400VAC Image #0
Zelio control relay for 3-phase detection of undervoltage and phase-fault 2C/O 8A 3x400VAC Image #1
Schneider Electric

Zelio control relay for 3-phase detection of undervoltage and phase-fault 2C/O 8A 3x400VAC

  • EAN no.: 3606480792175
  • LM no.: 7523007091
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no: RM22TU23

Promotion code: 80080463215

UNSPSC (v. 19.0501): 39122331

HS Code: 85364900

The Zelio RM22 control relay range brings to market 2 new key improvements.
- The backlight LED dials for adjustment makes it easy to use in any condition, even in dusty or poorly lit enviroments.
- The built-in testbutton simplifies commissioning and troubleshooting by a push of a button.

RM22TU23 is a controlrelay for measuring 3-phase sequence, fase fault detection and undervoltage.
The measurement is made directly through the supply terminals L1, L2 and L3 on the top of the relay.

The relay has 2 dials for setting up the relay.
On the top dial you select the measuring range from 380 to 480V.
The value is set to the voltage between 2 phases

The bottom dial adjust the maximal undervoltage in i % in reference to the measuring range set on the top dial.
The value can be between -2..-20%

The relay has 2 LED's on the front which indicates if a fault is detected (Def) and the state of the relay output (R).
The testbutton force the output when the timer is powered on.

Specifications

Voltage measuring range
304 - 576
With detachable clamps
FALSE
Phase failure detection
TRUE
Function under voltage detection
TRUE
Phase imbalance monitoring
FALSE
Function over voltage detection
FALSE
Phase sequence monitoring
TRUE
Voltage type (operating voltage)
AC
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0