Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC Image #0
Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC Image #1
Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC Image #2
Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC Image #0
Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC Image #1
Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC Image #2
Schneider Electric

Zelio control relay for current detection 0,15..15A 2C/O 8A 24-240VAC/DC

  • EAN no.: 3606480792304
  • LM no.: 7523007185
  • Supplier: Schneider Electric
Must login for adding to cart

Description

Type no: RM35JA32MR

Promotion code: 80080463215

UNSPSC (v. 19.0501): 39122331

HS Code: 85364900

The Zelio RM35 control relay range brings to market 2 new key improvements.
- The backlight LED dials for adjustment makes it easy to use in any condition, even in dusty or poorly lit enviroments.
- The built-in testbutton simplifies commissioning and troubleshooting by a push of a button.

RM35JA32MR is a control relay for current measurement.
The measurement is done through the M and E1/E2/E3 terminals which offers 3 measuring ranges:
M and E1 = 0,15-1,5 A
M and E2 = 0,5-5 A
M and E3 = 1,5-15 A
The control relay is supplied by 24 -240V AC/DC which makes it usable in most applications.

The relay has 4 illuminated dials for setting up the function of the relay.
On the top dial, you select the type of measurement that you want (overcurrent, undercurrent or a both at the same time).
You can also chose if the relay should remember the last measured value in case of a power cut (memory).
On the next dial, the measuring limit can be adjusted between 10 and 100% of the selected range.
The third dial set the hystereses which can be between 5 and 50%.
The bottom dial set the off-delay on the output which can be between 0,1 and 30 seconds.

The LED's on the front shows the status of the contacts.
The testbutton force the output when the timer is powered on.

Specifications

Min. adjustable off-delay time
0.1
Max. permitted off-delay time
30
With detachable clamps
FALSE
Contains function DC-voltage under current
TRUE
Single-phase overcurrent possible
TRUE
Three-phase overcurrent possible
FALSE
Current measuring range
0.15 - 15
Three-phase under current possible
FALSE
Single-phase under current possible
TRUE
Contains function DC-voltage overcurrent
TRUE

Manuals and guides