Schneider Electric
Zelio control relay for undervoltage and overvoltage detection 20..80VAC 1C/O 5A
- EAN no.: 3389119405157
- LM no.: 7523006283
- Supplier: Schneider Electric
Must login for adding to cart
Description
Type no: RM17UBE16
Promotion code: 80080463215
UNSPSC (v. 19.0501): 39122331
HS Code: 85364900
Zelio RM17 is a compact series of control relays which is easy to mount on a DIN-rail.
The relays are available for either 1 phase or 3 phase applications and are able to measure the voltage, current, phase-loss, phase-sequence and asymmetry between phases.
With a width of only 17,5 mm they only take up a very limited space on the DIN-rail and they also fit behind the cover of a standard panel.
RM17UBE16 is a control relay for measuring single pole voltage.
The relay can measure both overvoltage and undervoltage and it is measuring directly on the supply of the relay.
Voltage thresholds are set as a window function on each side of the measured value.
On the front of the relay are 3 dials for setting up the relay:
The first dial adjust the maximum overvoltage limit from 20..80 VAC/DC.
The second dial adjust the undervoltage limit from 20..80 VAC/DC.
The third dial adjust the delay of the output from 0,1..10 seconds.
RM17UBE16 has a fixed hysteresis of 3%
The control relay has a 1 C/O output contact with a maximum load of 5A.
On the front of the relay is 2 LED's for indication of the relay status.
The green LED indicates that the supply is present and the yellow LED indicates the status of the relay output.
The relays are available for either 1 phase or 3 phase applications and are able to measure the voltage, current, phase-loss, phase-sequence and asymmetry between phases.
With a width of only 17,5 mm they only take up a very limited space on the DIN-rail and they also fit behind the cover of a standard panel.
RM17UBE16 is a control relay for measuring single pole voltage.
The relay can measure both overvoltage and undervoltage and it is measuring directly on the supply of the relay.
Voltage thresholds are set as a window function on each side of the measured value.
On the front of the relay are 3 dials for setting up the relay:
The first dial adjust the maximum overvoltage limit from 20..80 VAC/DC.
The second dial adjust the undervoltage limit from 20..80 VAC/DC.
The third dial adjust the delay of the output from 0,1..10 seconds.
RM17UBE16 has a fixed hysteresis of 3%
The control relay has a 1 C/O output contact with a maximum load of 5A.
On the front of the relay is 2 LED's for indication of the relay status.
The green LED indicates that the supply is present and the yellow LED indicates the status of the relay output.