Log-in lemu.dk

Your access to more than 300,000 different products and a wide range of services

Enter your e-mail address and have your password sent to you:

Cancel
en

MS132-1.0T Circuit-breaker for primary transformer protection,Trip Class 10

ABB
{{StockInfo.NotAllowedReason}}
{{stck.StockInfo.RemoteStockLocation.DisplayName}} {{stck.StockInfo.RemoteStockLocation.Amount|number}} {{stck.StockInfo.RemoteStockLocation.Uom}} ({{stck.StockInfo.RemoteStockLocation.DeliveryTimeTxt}})
{{stck.StockInfo.CentralStockLocation.Amount|number}} {{stck.StockInfo.CentralStockLocation.Uom}} {{stck.StockInfo.CentralStockLocation.DisplayName}}
{{stck.StockInfo.CentralStockLocation.DisplayName}} (In stock)
{{stck.StockInfo.CentralStockLocation.DisplayName}} (Not in stock)
{{stck.StockInfo.CentralStockLocation.DeliveryTimeTxt}}
[{{stck.StockInfo.PrimaryStockLocation.DeliveryTimeTxt}}]
{{stck.StockInfo.NotCentralStockDeliveryTimeMsg}}
{{stck.StockInfo.SecondaryStockLocation.DisplayName}}: {{stck.StockInfo.SecondaryStockLocation.Amount|number}} {{stck.StockInfo.SecondaryStockLocation.Uom}}
Special return conditions

Product description

Type no.:
LM no.:
Own product no.:
1SAM340000R1005
7822413195
-
Discount code:
UNSPSC Code:
Customs code:
80080808011
39121616
85362010
The circuit breaker for transformer protection MS132-1.0T is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 1.0 A. It allows fuse-less protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 100 kA at 400 VAC and a trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, power in-feed blocks are available as accessory.
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu1
Number of poles3
Overload release current setting0.6 - 1
Number of auxiliary contacts as change-over contact0
Rated voltage690 - 690
Degree of protection (IP)IP20
Position of connection for main current circuitFront side
Motor drive integratedNo
Type of electrical connection of main circuitScrew connection
Type of control elementTurn button
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100
Adjustment range undelayed short-circuit release20 - 20
Suitable for DIN rail (top hat rail) mountingYes
Integrated earth fault protectionNo
Motor drive optionalNo
With under voltage releaseNo
Device constructionComplete device in housing
DIN rail (top hat rail) mounting optionalYes
Complete device with protection unitYes
;